110 Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012
Chapter 1 Drive Comparisons
Table 12 - User Device Connections to the Regulator Board Terminal Strip
User Device Regulator Board Terminal Number
Run 1 (+24V), 2
Stop 1 (+24V), 3
Jog 1 (+24V), 4
Reverse/Forward 1 (+24V), 5
Auto/Manual 1 (+24V), 6
Interlock 9, 11 (+24V)
Fault/Alarm Reset 10, 11 (+24V)
Digital Input 0 12, 11 (+24V)
Motor Thermostat 13, 11 (+24V)
Speed Reference Potentiometer
• High Side (+10 ISOL)
• Wiper (+ Man. Ref.)
• Low Side (– Man. Ref.)
16
17
18
Auto Reference
• (+)
• (–)
19
20
Tachometer (Analog)
(1)
High Range
(2)
Low Range
(2)
Common
(2)
(1) Analog tachometer must be rated between 18…200 V/1000 RPM. The output voltage must not
exceed 250V for a DC tachometer or 275 RMS for AC tachometers when the motor is rotating at the
value set for the TOP SPEED parameter. To calculate the output voltage at top speed: Tachometer
Voltage at Top Speed = (Top Speed / 1000) x (Analog Tach Voltage / 1000). See the User Manual
for information on jumpers J14 and J11.
(2) When the maximum tachometer voltage at top speed is 62VDC, use terminals 22 and 23 to
connect the analog tachometer. When the maximum tachometer voltage at top speed is 250VDC,
use terminals 21 and 23 to connect the analog tachometer.
21
22
23
Meter output 1 24, 25 (Common)
Meter output 2 25 (Common), 26
Running (Indicator) 27, 28
Alarm (Indicator) 29, 30
No Fault (Indicator) 31, 32