Publication 1734-UM015A-EN-E - November 2009
DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet 45
4. Enter the slot number in the Slot box.
It is not possible to make a Rack connection to the Point I/O
DeviceLogix module. The connection must be a direct one.
On the Connection tab, you can change the Requested Packet Interval
(RPI), the default is 20 ms.
The Module Info tab will display the status and identity information of
the module when the module is online.
There is no tab for configuration. Configuration of the Point I/O
DeviceLogix modules is done only using RSNetworx for DeviceNet.
See Chapter 6
for more details.
RSLogix 5000 will create the following input tags:
AdapterName:SlotNumber:I.Data
AdapterName:SlotNumber:I.LogicDefinedData
AdapterName:SlotNumber:I.Status.LogicEnabled
AdapterName:SlotNumber:I.Status.Owned
AdapterName:SlotNumber:I.PeerMissing
AdapterName:SlotNumber:I.LogicDefinedIntData[0...7]
RSLogix 5000 will create the following output tags:
AdapterName:SlotNumber:O.Data
AdapterName:SlotNumber:O.LogicDefinedData
AdapterName:SlotNumber:O.LogicDefinedIntData[0...7]