12 ControlLogix™ Voltage/Current Input Module
Publication
1756-IN039D-EN-P - February 2003
Wire the Module
You can only connect wiring to your module through an RTB or IFM.
The example below shows how to wire the module.
40912-M
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
Shield
ground
Channel 0
Channel 3
Jumper
wires
i
i
A
2-Wire
Transm itter
A
1756-IF16 Differential current wiring example
IN-0
IN-1
IN-2
IN-3
IN-7
RTN
IN-4
IN-5
IN-6
IN-15
IN-8
IN-9
IN-10
IN-11
RTN
IN-12
IN-13
IN-14
i RTN-0
i RTN-1
i RTN-2
i RTN-3
i RTN-7
RTN
i RTN-4
i RTN-5
i RTN-6
i RTN-15
i RTN-8
i RTN-9
i RTN-10
i RTN-11
RTN
i RTN-12
i RTN-13
i RTN-14
1. Use the following chart when wiring your module in differential mode
2. When operating in 4 channel, high speed mode, only use channels 0, 2, 4 and 6.
3. All terminals marked RTN are connected internally.
4. A 249
W current loop resistor is located between IN-x and i RTN-x terminals.
5. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to
terminal to maintain the module’s accuracy.
This channel: Uses these terminals: This channel: Uses these terminals:
Channel 0 IN-0 (+), IN-1 (-) & i RTN-0 Channel 4 IN-8 (+), IN-9 (-) & i RTN-8
Channel 1 IN-2 (+), IN-3 (-) & i RTN-2 Channel 5 IN-10 (+), IN-11 (-) & i RTN-10
Channel 2 IN-4 (+), IN-5 (-) & i RTN-4 Channel 6 IN-12 (+), IN-13 (-) & i RTN-12
Channel 3 IN-6 (+), IN-7 (-) & i RTN-6 Channel 7 IN-14 (+), IN-15 (-) & i RTN-14
NOTES: