Publication DNET-UM004A-EN-P - March 2004
1-6 Before You Begin
To choose a scanner, use the following table:
Bridging Across Networks
Logix5000™ devices can usually communicate with devices on other
networks with no additional configuration or programming.
A bridge connects two different networks. The bridge is either:
single device with communication ports for two different
networks
separate communication devices in the same chassis
For example, the bridge device shown below is connected to
both EtherNet/IP and DeviceNet networks. Device 1 on
EtherNet/IP can communicate with Device 2 on DeviceNet
through the bridge.
If you are using: And: Use this scanner:
single network CompactLogix™ controller CompactLogix 1769-SDN
ControlLogix® controller ControlLogix 1756-DNB
DriveLogix™ controller DriveLogix and FlexLogix 1788-DNBO
FlexLogix™ controller
SoftLogix™ 5800 controller SoftLogix5800 1784-PCIDS
subnets EtherNet/IP main network EtherNet/IP to DeviceNet Linking Device 1788-EN2DN
ControlNet main network ControlNet to DeviceNet Linking Device 1788-CN2DN
EtherNet/IP network
DeviceNet network
switch
Device 1
Device 2
bridge