Allen-Bradley 1794-IE8H Manual de usuario Pagina 79

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 146
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 78
Publication 1794-UM063A-EN-P - March 2006
Calibrate Your Module 5-11
1794-OE8H Calibration
Features
The following features are unique to the 1794-OE8H module:
There are six values per channel that the I/O module uses to calculate
the corresponding calibration values (offset and gain).
Min Scale DAC at 1500
dec
about 1 mA
Max Scale DAC at 6700
dec
about 20 mA
Current-read-back Min Scale at 1500
dec
about 1 mA
Current-read-back Max Scale at 6700
dec
about 20 mA
Voltage-read-back Min. Scale at 1500
dec
Voltage-read-back Max Scale at 6700
dec
The module internally calculated calibration values are:
Offset DAC
Gain DAC
Offset I-read-back
Gain I-read-back
Offset U-read-back
Gain U-read-back
All calibration values are stored in the module nonvolatile EEPROM.
Only one channel can be calibrated at a time according to one
calibration value (max scale or min scale values).
The actual date must be transmitted after calibration to the I/O module
and stored in the module nonvolatile EEPROM. The data can be read
out over the EDT channel.
The whole calibration can be set to default values by sending a reset
command. The default date is Jan,01,2000.
A specified calibration value can be set to default by sending a reset
command for that channel.
There is a special command to store the whole calibration data from
RAM to EEPROM within the I/O module.
If one value, except the calibration date, isn’t calibrated yet, or if you set
one value to default, the I/O module displays a calibration error within
the Real Time Data diagnostic field.
Vista de pagina 78
1 2 ... 74 75 76 77 78 79 80 81 82 83 84 ... 145 146

Comentarios a estos manuales

Sin comentarios