Allen-Bradley ControlLogix Manual de usuario Pagina 5

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 10
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 4
CalAmpWirelessNetworksTechnicalSupport|Tel507.833.8819|Email[email protected] Page5of10
aresentforeachcloseandreopenoftheTCPconnection.Thisaddsalotofonairtrafficandimpactsthesystem
performance.
NotewhenusingdifferentinactivitytimeoutvaluesformessageswiththesameTCPconnection:
WhendifferentmessagesforthesameremotesharethesameTCPconnection,
eachdifferentmessage’sinactivitytimeout
wouldrestartthetimeouttimer.Messageexample:msg1inactivity60,msg2inactivity100,msg3inactivity30.These
messagesarethensentasfollows:msg1issent,msg2issent,msg3andthenawaitisdone.Sincethelastmessagewas
msg3withinactivitytimeout
of30seconds,theTCPconnectionwouldcloseafter30secondsofmsg3.
Settingexampleusingcustominactivitytimeout(100sec).
SummaryonTCPconnectiontimeout(inactivitysetting)
SincethelongestinactivitytimeoutperTCPconnectionwitharemoteunit(PLC/RTU)is120seconds(basedonmessage
inactivitymaxof120seconds),itisimportantthateachremote(PLC/RTU)ispolledwiththe120secondperiodtoavoid
extratrafficresultingfromadditionalTCP/IPopenandcloseconnection
messages.Forsystemswherepollingisdone
infrequently(>120sec)theadditionalTCPtrafficneedstobeconsideredforthesystemtrafficplan.
Fornormaloperationtheinactivitytimeoutdoesnotneedtobespecifiedinthe“Path”setting.Masterandremotesshould
besetthisway,especiallyifremote
PLCssendunsolicitedmessagesorinitiatecommunicationwithotherremotes.Ifa
systemhasamixofPLCs(CompactLogix/ControlLogixwithMicroLogix/SLC),thenalsorefertoCalAmp’s“AllenBradleyPLC
forViperSystem”supportbulletinavailableonCalAmp’sWEBsiteundersupport.

Vista de pagina 4
1 2 3 4 5 6 7 8 9 10

Comentarios a estos manuales

Sin comentarios