Allen-Bradley ControlLogix Manual de usuario Pagina 164

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 212
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 163
164 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Chapter 10 Develop Applications
Interrupt the Execution of Logic and Execute the Fault Handler
Dependent on your application, you can want an I/O connection error to cause
the Controller Fault Handler to execute. To do so, set the module property that
causes a major fault to result from an I/O connection error. The major fault
causes the execution of the Controller Fault Handler.
First, develop a routine in the Controller Fault Handler that can respond to I/O
connection faults. Then, in the Module Properties dialog box of the I/O module
or parent communication module, check Major Fault On Controller If
Connection Fails While in Run Mode.
Figure 41 - I/O Connection Fault Causes Major Fault
For more information about programming the Controller Fault Handler, see the
Major, Minor, and I/O Faults Programming Manual, publication 1756-PM014
.
Parent Communication Module Properties
I/O Module Properties
Vista de pagina 163
1 2 ... 159 160 161 162 163 164 165 166 167 168 169 ... 211 212

Comentarios a estos manuales

Sin comentarios