Allen-Bradley ControlLogix Manual de usuario Pagina 95

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 212
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 94
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 95
Communication Networks Chapter 5
Data Highway Plus (DH+)
Network Communication
For DH+ network communication, you have two module options for use in the
ControlLogix chassis. Tab l e 20
lists the DH+ modules and capabilities.
For DH+ network communication, use a 1756-DHRIO or 1756-DHRIOXT
module in the ControlLogix chassis to exchange information between these
controllers:
PLC and SLC controllers
ControlLogix controllers and PLC or SLC controllers
ControlLogix controllers
The DH+ network also provides the following:
Data exchange between controllers
Plant-wide data sharing
Cellular level data sharing
You can connect a maximum of 32 stations to one DH+ link:
Channel A supports 57.6 Kbps, 115.2 Kbps, and 230.4 Kbps.
Channel B supports 57.6 Kbps and 115.2 Kbps.
Table 20 - DH+ Modules and Capabilities
RIO Module Is used to
1756-DHRIO Function as a remote I/O (RIO) scanner.
Support 32 logical rack connections or 16 block transfer connections per channel.
Establish connections between controllers and I/O adapters.
Distribute control so that each controller has its own I/O.
1756-DHRIOXT Function as a remote I/O (RIO) scanner.
Support 32 logical rack connections or 16 block transfer connections per channel.
Establish connections between controllers and I/O adapters.
Distribute control so that each controller has its own I/O.
Operate in extreme environments with -25…70 °C (-13…158 °F) temperatures.