132 Calibrate Your Analog Modules
Both channel status indicators turn off.
8. Apply 0.0V to the input.
9. Click Accept Low Calibration.
10. Click the Download to Device button.
The status indicator for the channel being calibrated blinks.
11. Set the voltage source to +10.0V.
12. Click Accept High Calibration.
13. Click the Download to Device button.
Calibration is complete as soon as High and Low calibration for the
selected channels are done successfully.