Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
222 Configure POINT I/O Modules for DeviceNet Networks
5. From the Device Parameters dialog, set Run or Idle, noting that any
parameter with a lock indicated next to it is nonchangeable..
6. Select values for current or voltage.
For current, click one of the following:
4…20 mA
0…20 mA
For voltage, click one of the following:
0…10V
-10…+10V
Note that fault states include the following:
Hold Last state
Go to Low Clamp
Go to High Clamp