Publication 1734-UM011D-EN-P - May 2011
104 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-IR2
2 Channel RTD Input
Configuration Data Data Type Default Value Valid Data Values
Low Engineering Channel 0 INT 1,000 -32,768…32,767
High Engineering Channel 0 INT 5,000 -32,768…32,767
Digital Filter Channel 0 INT 0 0…10,000 ms
Low Alarm Limit Channel 0 INT -32,768 -32,768…32,767
High Alarm Limit Channel 0 INT 32,767 -32,768…32,767
Low Low Alarm Limit Channel 0 INT -32,768 -32,768…32,767
High High Alarm Limit Channel 0 INT 32,767 -32,768…32,767
Limit Alarm Latch Channel 0 SINT 0 0=No Latching
1=Alarms Latch
Alarm Disable Channel 0 SINT 0 0=Alarms Enabled
1=Alarms Disabled
Sensor Type Channel 0 SINT 1 0=Ohms
1=100 Pt α 385
2=200 Pt α 385
5=100 JPt α 3916
6=200 JPt α 3916
9=10 Cu α 427
10=120 Ni α 672
11=100 Ni α 618
12=120 Ni α 618
Temperature Mode Channel 0 SINT 1 0=Custom Scale
1=°C
2=°F
3=°K
4=°R
Low Engineering Channel 1 INT 1,000 -32,768…32,767
High Engineering Channel 1 INT 5,000 -32,768…32,767
Digital Filter Channel 1 INT 0 0…10,000 ms
Low Alarm Limit Channel 1 INT -32,768 -32,768…32,767
High Alarm Limit Channel 1 INT 32,767 -32,768…32,767
Low Low Alarm Limit Channel 1 INT -32,768 -32,768…32,767
High High Alarm Limit Channel 1 INT 32,767 -32,768…32,767
Limit Alarm Latch Channel 1 SINT 0 0=No Latching
1=Alarms Latch
Alarm Disable Channel 1 SINT 0 0=Alarms Enabled
1=Alarms Disabled