Publication 1734-UM011D-EN-P - May 2011
LED Status Indicators 65
System Power
Off Not active; field power is off or
DC-DC converter problem
present.
1. Verify power is on, and apply
power if needed.
2. Verify backplane power not
exceeded, and correct.
3. Replace 1734-AENT module.
Green System power is on; DC-DC
converter is active (5V).
None
Field Power
Off Not active; field power is off. Apply field power.
Green Power is on; 24V is present. None