Publication ENET-UM001I-EN-P - January 2010 195
Status Indicators Appendix A
1738-AENTR ArmorPOINT
I/O 2-port EtherNet/IP
Adapter Status Indicators
The 1738-AENTR ArmorPOINT I/O 2-port EtherNet/IP adapter has
several status indicators.
1738-AENTR ArmorPOINT I/O 2-port EtherNet/IP Adapter Status Indicators
The 1738-AENTR adapter does not display scrolling messages.
Link 1 Activity/Status Indicator
Link 2 Activity/Status Indicator
Adapter Status Indicator
Network Activity Indicator
Network Status Indicator
POINTBus Status Indicator
System Power Indicator
Adapter Power Indicator
Link 1 or Link 2 Activity/Status Indicator
Indicator Status Description
Link 1 or
Link 2
A
ctivity
/Status
Off No link established. Verify network cabling and correct, if necessary.
Green Link established at 100 Mbps. No action is required.
Flashing green Transmit or receive activity present at 100 Mbps. No action is required.
Yellow Link established at 10 Mbps. No action is required.
Flashing yellow Transmit or receive activity present at 10 Mbps. No action is required.