208 Publication ENET-UM001I-EN-P - January 2010
Appendix A Status Indicators
2. Program the controller or peer device to recognize and transmit I/O or
make a messaging connection to the adapter.
3. Configure the adapter for the program in the controller or the I/O from
t
he peer device.
If the NET B statu
s indicator is off and the NET A indicator is off,
take the following actions.
1. Securely connect the adapter to the drive using the Internal Interface
(ribb
on) cable and to the network using an Ethernet cable.
2. Correctly connect the Ethernet cable
to the Ethernet connector.
3. Set a unique IP address using a BOOTP
server or by disabling BOOTP
and using adapter parameters.
If the NET B statu
s indicator is off and the NET A indicator is
solid red, take the following actions.
1. Configure the adapter to use a unique IP address.
2. Cycle power to the adapter.
If t
he NET B statu
s indicator is off and the NET A indicator is
flashing red/green or red, take the following actions.
1. Check the IP address in the adapter and scanner, and verify that the
c
ontroller can communicate with the adapter.
2. Ping the adapter.