Allen-Bradley Rockwell Automation 1734-AENT Manual de usuario Pagina 201

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 230
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 200
Publication ENET-UM001I-EN-P - January 2010 201
Status Indicators Appendix A
20-COMM-E Module
Status Indicators
The 20-COMM-E module has four status indicators.
20-COMM-E Status Indicators
PORT - DPI Connection Status
MOD - Adapter Status
NET A - EtherNet/IP Connection Status
NET B - EtherNet/IP Transmit Status
Module Status Indicator
Indicator Status Description
PORT Off The adapter is not powered or is not properly connected to the drive.
Follow the corrective action below.
Flashing red The adapter is not receiving a ping message from the drive.
Follow the corrective action below.
Solid Red The drive has refused an I/O connection from the adapter. Another DPI
peripheral is using the same DPI port as the adapter.
Another DPI peripheral is using the same DPI port as the adapter.
Follow the corrective action below.
Orange The adapter is connected to a product that does not support Allen-Bradley DPI
communication.
Connect the adapter to a product that supports Allen-Bradley DPI
communication (for example, a PowerFlex 7-Class drive).
Flashing Green The adapter is establishing an I/O connection to the drive. No action is
required.
Solid Green The adapter is properly connected and is communicating with the drive. No
action is required.