2-8 Installation and Wiring
Capacitive Current Coupling
High speed voltage switching causes AC coupling from motor cables to ground
terminal/protective earth. The current produced by this coupling is referred to as
capacitive current. The drive current is the combination of capacitive current and
motor current. Because motor current is monitored for overload protection, the
table below lists the maximum cable length recommendations that will assure a
capacitive current error of less than 15 percent.
Cable Length Recommendations — Capacitive Current Table 2.F
Not recommended for use above 4 kHz PWM Frequency.
When using shielded cable at lightly loaded conditions, cable length recommendations for drives rated 0.75 kW (1 HP) and
below are 61 meters (200 feet).
Not recommended for 230V applications.
380-460V
Ratings
kHz Motor Cable Only RWR at Drive
Reactor at Motor
Shielded
Unshielded Shielded
Unshielded Shielded
Unshielded
feet meters feet meters feet meters feet meters feet meters feet meters
4.0 kW
(5 HP)
2 350 107 600 183 300 91.5 600 183 400 122 600 183
4 425 130 600 183 350 107 600 183 450 137 600 183
8 475 145 500 152
450 137 500 152
2.2 kW
(3 HP)
2 360 110 600 183 280 85.4 600 183 400 122 600 183
4 375 114 600 183 275 83.8 600 183 400 122 600 183
8 400 122 500 152
400 122 500 152
1.5 kW
(2 HP)
2 300 91.5 550 168 275 83.8 600 183 300 91.5 600 183
4 300 91.5 550 168 275 83.8 600 183 300 91.5 500 152
8 325 99.1 500 152
350 107 500 152
0.75 kW
(1 HP)
2 200 61 375 114 200 61 425 130 225 68.6 400 122
4 225 68.6 375 114 200 61 425 130 225 68.6 375 114
8 250 76.2 375 114
225 68.6 400 122
0.55 kW
(0.75 HP)
2 180 54.9 350 107 180 54.9 375 114 180 54.9 350 107
4 180 54.9 350 107 180 54.9 375 114 180 54.9 350 107
8 180 54.9 350 107
180 54.9 350 107
0.37 kW
(0.5 HP)
2 100 30.5 325 99.1 100 30.5 350 107 100 30.5 300 91.5
4 100 30.5 325 99.1 100 30.5 350 107 100 30.5 350 107
8 100 30.5 325 99.1
100 30.5 350 107
200-240V Ratings No Reactor RWR at Drive
Reactor at Motor
0.37 to 4.0 kW
(0.5 to 5 HP)
2 through 8 kHz
Shielded
Unshielded Shielded
Unshielded Shielded
Unshielded
feet meters feet meters feet meters feet meters feet meters feet meters
525 160 600 183
525 160 600 183