Specifications A-3
Control Features
PWM Algorithm Sine Weighted PWM with Harmonic Compensation
Switching Device IGBT
V/Hz Ratio Programmable
Carrier Frequency Adjustable from 2 to 8kHz in 100 Hz Increments (Factory Default is 4kHz)
DC Boost Adjustable Select from a Family of Boost Curves
Current Limiting Software Controlled, Coordinated for Drive and Motor Protection — Programmable
from 1 to 180% of Drive Output Current
Motor Protection I
2
t Overload Protection 150% for 60 Seconds, 200% for 30 Seconds
Overload Pattern #0 Flat Response Over Speed Range (No Speed Compensation)
Overload Pattern #1 Speed Compensation Below 25% of Base Speed
Overload Pattern #2 Speed Compensation Below 100% of Base Speed
Accel/Decel Time(s) 0.1 to 600 Seconds
S-Curve Accel/Decel Time(s) 0 to 100% of Accel/Decel Time Not to Exceed 60 Seconds
Stopping Modes 4 Programmable Modes:
Ramp to Stop 0.1 to 600 Seconds
Coast to Stop Stops All PWM Output
DC Injection Braking Applies DC Voltage to the Motor for 0 to 25 Seconds
DC Injection Braking with Auto Stop
Protective Features
Overcurrent Programmable limit, 200% of Hardware Limit, 300% of Instantaneous Fault
Excessive Temperature Embedded Temperature Sensor Trips if Heatsink Temperature Exceeds 95
°
C
Over/Under Voltage DC bus voltage is monitored for safe operation.
For 200-240VAC input drives, the overvoltage trip occurs at a bus voltage of 400VDC
(equivalent to a 290VAC incoming line voltage).
For 380-460VAC input drives, the undervoltage trip occurs at a bus voltage of
800VDC (equivalent to a 575VAC incoming line voltage).
For 200-240VAC input drives, the undervoltage trip occurs at a bus voltage of
210VDC (equivalent to a 150VAC incoming line voltage).
For 380-460VAC input drives, the undervoltage trip occurs at a bus voltage of
390VDC (equivalent to a 275VAC incoming line voltage).
Control Ride Through
Minimum Ride Through is 0.5 Seconds Typical Value is 2 Seconds
Ground Short Any Output Phase to Ground Short
Faultless Ride Through 100 Milliseconds
Output Short Circuit Any Output Phase to Phase Short