Parameters and Programming 5-13
69 [Accel Time 2]
Time for the drive to ramp from 0.0 Hz to P33 - [Maximum Frequency]. The rate
is linear for any increase in command frequency unless P53 - [S-Curve] is set to
a value other than 0. Setting this to 0.0 gives 0.1 seconds acceleration with the
initial current limit turned off. This allows quicker acceleration times for low inertia
systems. For medium to high inertia systems, the minimum value should be 0.1.
0.0/600.0 0.1 Sec. 20.0
Seconds
70 [Decel Time 2]
Time for the drive to ramp from P33 - [Maximum Frequency] to 0.0 Hz. The rate
is linear for any decrease in command frequency unless P53 - [S-Curve] is set to
a value other than 0.
0.1/600.0 0.1 Sec. 20.0
Seconds
71 [IR Compensation]
The programmed value adds a voltage to the output based on the torque current.
An additional 31 volts (150%) is added to 460 volt units to compensate for stator
resistance. 15.5 volts (150%) is added for 230 volt units. If the drive trips on an
F07 - [Motor Overload] fault, or has trouble accelerating to commanded speed,
this value should be reduced. A setting of 0% disables this function.
0/150
1% 50%
72 [Slip Compensation]
This parameter compensates for the inherent slip in an induction motor. A fre-
quency is added to the commanded output frequency based on torque current.
If motor shaft speed decreases significantly under heavy loads then this value
should be increased. A setting of 0.0 Hz disables the function.
0.0/5.0 0.1 Hz 2.0 Hz
73 [Reverse Disable]
When this parameter is set to a 1, reverse is disabled. The reverse command may
come from the analog input, TB3-5, the keypad or a serial command. With a
negative analog input and reverse disabled, the frequency command will be zero
in bipolar mode and minimum frequency in unipolar mode. All digital reverse inputs
including two-wire Run Reverse will be ignored with reverse disabled.
Important: This parameter cannot be programmed while the drive is running.
0/1
Numeric
value
0
74 [Analog Select]
Settings: 0 = unipolar analog input 0 to +10V
1 = bipolar analog input -10 to +10V
Important: With this parameter set to bipolar (setting 1), the parameter settings
for P75 - [Analog Input Minimum] and P32 - [Minimum Frequency]
are ignored. In addition, all other reverse inputs (program keypad
module, TB3-5 control terminal block, or serial communication
module) are ignored with the exception of when P46 - [Input Mode]
is programmed to setting 7. (This applies to drives with firmware
version FRN 7.03 and later.) When P46 - [Input Mode] setting 7 is
active, and TB3-8 is closed, the frequency source is P58 - [Internal
Frequency] and the direction will be commanded from the control
terminal block (either terminal TB3-5 or TB3-6).
Important: This parameter cannot be programmed while the drive is running.
0/1 Numeric
value
0
Program Group
No. Parameter Name/Description
Min./Max.
Range
Units
Factory
Default
This parameter applies only to the Analog Signal Follower model.