5-10 Parameters and Programming
49 [PWM Frequency]
Carrier frequency for the PWM output waveform. The chart below provides
derating guidelines based on the PWM frequency setting.
Important: Ignoring derating guidelines can cause reduced drive performance.
2.0/8.0 0.1 kHz 4.0 kHz
50 [Restart Tries]
Maximum number of times the drive will attempt to reset a fault.
Faults 03 – 20 will automatically reset according to this parameter setting.
0/9 Numeric
Value
0
51 [Restart Time]
Time between restart attempts.
If this parameter and P50 - [Restart Tries] are both set to zero, and P46 - [Input
Mode] is not set to 3, the auto fault clear feature is enabled. This feature
automatically clears overvoltage, undervoltage, and overtemperature faults 1
second after the fault condition is removed.
If this parameter is set to zero and P50 - [Restart Tries] is not zero, then the time
between restart attempts is 1 second.
0.0/300.0 0.1
Seconds
10.0
Seconds
52 [DB Enable]
Enables/disables external dynamic braking.
Setting “0” = Disable. Settings 1 through 100 = % duty cycle braking.
This parameter cannot be programmed while the drive is running.
0/100 Numeric
Value
0
Program Group
No. Parameter Name/Description
Min./Max.
Range
Units
Factory
Default
12345678
84
86
88
90
92
94
96
98
100
% Output Current (A)
Carrier Frequency (kHz)
ATTENTION: The 160 Dynamic Brake Module is rated for 5%
duty cycle. Use of this package above 5% should not be used and
voids the UL rating of this device. When setting this parameter
to a value above 5% duty cycle, the resistor must be sized to avoid
overheating of the resistor package.