126 Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012
Chapter 1 Drive Comparisons
Figure 96 - I/O Converter Board M_IN Terminal Block Designations
Table 31 - I/O Converter Board M_OUT Terminal Block Designations
No. Signal Description
1 Digital Input 1 Rated input voltage:115V AC ±10% 50 -
60Hz.
ON input voltage: 115V AC ±10%
OFF input voltage: 0 - 70V AC
ON input current: 4 - 5.5mA
2 Digital Input 2
3 Digital Input 3
4 Digital Input 4
5 Digital Input 5
6 Digital Input 6
7 Digital Input 7
8 Digital Input 8
Co
m
Digital Input Common
No. Signal Description
24V +24VDC Supply 24V DC ±10%, 40 mA power supply. max
load 120 mA.
Supply power can be provided by the +24V
DC supply on the Control board I/O (terminal
19 - see Figure 97
on 127) or an external
source (see Figure 98 on page 127).
1 Digital Output 1 Output type: Open collector, PNP type with
15kohm pull-down
Output current: 10 mA max.
Delay time hw OFF to ON: 5 ms (typ.)
Delay time hw ON to OFF: 50 ms (typ.)
2 Digital Output 2
3 Digital Output 3
4 Digital Output 4
5 Digital Output 5
6 Digital Output 6
7 Digital Output 7
8 Digital Output 8
0V 24V Common Common for the power supply.
• If an internal supply is used, this terminal
must be wired to the digital input
common (terminal 16 or 35) on the
Control board I/O. See Figure 97
on 127.
• If an external supply is used, this
terminal must be wired to the external
24V DC supply common and the digital
input common (terminal 16 or 35) on the
Control board I/O. See Figure 98
on page
127.
Comentarios a estos manuales