Allen-Bradley 1770-M10 Especificaciones Pagina 95

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 194
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 94
Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012 95
Drive Comparisons Chapter 1
Figure 65 - 1395 - TB3 Terminal Descriptions
Encoder
Channel A
Channel A
Channel B
Channel B
+ Supply Voltage
- Supply Voltage
TB3
Main Control
Board
Power Stage
Interface Board
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
24V DC E-Coast
Drive FLT Output
Closed when the
drive is not faulted
115V AC E-Coast
115V AC Common
24V DC or 115V AC
Voltage Source
COM
Motor Thermostat
(2)
Reset
(1)
(1) If parameter 620 = 0, then the Reset input requires a N.O. push button as shown here:
Closing the push button causes System Reset to occur.
This is the default value for the 1395.
If parameter 620 = 1, then the Normal Stop input requires a N.C. push button as shown here.
Opening the push button causes Normal Stop to occur.
(2) If no thermostat is used, 115V AC or 24V DC must still be applied to TB3, terminal 2.
Note: If a N.C. push button is used and parameter 620 = 0, the drive will be in a continuous reset condition.
If a N.O. push button is used and parameer 620 = 1, a Stop will be present in [Logic Cmd 1], parameter 150.
ENCA1
ENCA1
ENCB1
ENCB1
ENCPWR +12V
ENCGND 12V
–24V OUT
+24V OUT
–24V ECOAST
+24V ECOAST
FLT 2
FLT 1
115V COMMON OUT
115V ECOAST2
115V ECOAST1
RESET IN
MOTOR TEMP IN
COMMON
HOT
Vista de pagina 94
1 2 ... 90 91 92 93 94 95 96 97 98 99 100 ... 193 194

Comentarios a estos manuales