84 Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012
Chapter 1 Drive Comparisons
PowerFlex DC Field Converter Connections
For 575V or 690V AC input drives only, a step down transformer with either a
230 VAC secondary, for a 150V motor field, or 460 VAC, for a 300V motor field,
is required before the input to the field control circuit (terminals U1, V1).
Also, If the rated voltage of the DC motor field is not compatible with the field
DC output voltage of the drive, an external field control transformer must be
used. Refer to the following example for transformer selection information.
Example: 10 Hp, 240V Armature, 17.2A, 240V Field, 2.0 A motor
a. The field control transformer must have a 230V primary, a 460V
secondary, and be single-phase, 60 Hz
b. kVA = 2 A x 460VAC x 1.5 = 1.38 kVA (1.5 kVA is closest)
In addition, the following configuration must to completed in the
PowerFlex DC drive:
c. Control board DIP switch S14 must be set to select a value of 2 A.
d. Parameter 374 [Drv Fld Brdg Cur] must be programmed to match DIP
switch S14 = “2.”
e. Parameter 280 [Nom Mtr Fld Amps] must be programmed to the rated
motor nameplate field current “2.”
PowerFlex DC Field Converter Terminal Designations
PowerFlex DC Frames A…C Field Circuit Wire Sizes and Terminal Specifications
PowerFlex DC Frame D Field Circuit Wire Sizes and Terminal Specifications
Terminal Description
U1, V1 Single-phase AC line input power to the field circuit.
C1, D1 DC output power to the motor field.
Terminals Wire Size and Type
(1)
(1) See “Cable and Wiring Recommendations” in the PowerFlex Digital DC Drive User
Manual, publication 20P-UM001
, for cable spacing information.
Tightening Torque
N•m (lb•in)
U1, V1, C1, D1 24…10 AWG/kcmils 0.5…0.8 (4.4…7.1)
Drive Current Rating Code
(1)
(1) See PowerFlex Digital DC Drive on page 28, positions 8, 9 and 10 for corresponding drive HP rating, armature amp rating and field
amp rating.
Terminals Wire Size
(2)
(2) See “Cable and Wiring Recommendations” in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for cable spacing
information.
Tightening Torque
N
•m (lb•in)
230V 460V 575V 690V
875 830 810 678 U1, V1, C1, D1 6 AWG 4.0 (35.4)
1K0 996 1K0 791
–– 1K2904
–– 1K31K0
–– 1K6–
– 1K1 – 1K1 2 AWG
– 1K3 – 1K2
– 1K4 – 1K4
–––1K5