54 Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012
Chapter 1 Drive Comparisons
Power Comparisons
1395 Power Connections - Standard Field Voltage
Figure 19 - 1395 - 1…30 Hp, 230VAC / 2…60 Hp, 460VAC Series
ATTENTION: The motor field supply is phase sensitive. To guard against
possible drive/motor damage, assure that the connections are properly made
according to Figure 19
, Figure 20 on page 55, Figure 21 on page 55, and
Figure 22 on page 56
.
IMPORTANT
If the AC input power system does not have a neutral or one phase referenced
ground, an isolation transformer with the neutral of the secondary grounded is
highly recommended. If the line-to-line voltages on any phase can exceed
125% of the nominal line-to-line voltage, an isolation transformer with the
neutral of the secondary grounded, is always required.
A1+ A2
L1 L2 L3
M
A2A1
DC contactor
PE
Line reactor or isolation transformer
F1 F2 F3
Factory wiring
Factory wiring
Front view of drive
TB1
12 3 4
F1+ F2-
DC motor shunt field*
*Typical motor connection.
Refer to motor data for specific motor connections.
DC motor armature