184 Rockwell Automation Publication XXXX-X.X.X - Month Year
Chapter 3 Network Communication
Parameter 100: Logic Status [Logic Status]
Internal Units: None
Programming Terminal units: Bit Field
Description: This is a word of status data that indicates conditions within the
Drive in boolean logic. Where a bit is set to 1, the corresponding condition in the
drive is true, otherwise the condition is false. The bits in the Logic Status word
are defined as:
Fault Field 0, 1 (Bits 0, 1): This 2-bit field denotes the fault status of the drive as
follows:
Active Logic Command 0,1 (Bits 2,3): This 2-bit field denotes the logic
command the drive is acting upon as follows:
See Chapter 7, Programing and Parameters, of the Bulletin 1395 Digital DC
Drive User Manual, publication 1395-UM003
. for more details.
Flt. Fld. 1 Flt. Fld. 0 Definition
00No Fault
0 1 Warning Fault
10Soft Fault
11Hard Fault
Logic CMD 1 Logic CMD 0 Definition
0 1 Parameter 150
0 0 Parameter 151
1 1 Parameter 152