Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012 151
Drive Comparisons Chapter 1
Figure 105 - Frame C Regenerative Drive - Leg Fuse Location
Figure 106 - Frame D Regenerative Drive - Leg Fuse Location
Fuses for Non-Regenerative Frame C and D Drives
AC input line and/or leg fuses are internally mounted and provided with frames
C and D drives. See Fuse Code FS4 in Frame C and D Fuse Designations on page
146
. Also, see Frame C Non-Regenerative Drive - AC Input Line Fuse Location
on page 153
.
Table 57 - Recommended AC Input Line Fuses - 230V AC Input Frame C
Note: Drive shown with front covers removed and
Control EMI shield lowered.
Leg fuses and switches are located on the bus bars behind the Control EMI
shield, which holds the Control board.
Note: Drive shown with Control EMI
shield in open position.
Leg fuses and switches are located on the bus bars behind the Control EMI
shield, which holds the Control board.
Frame Drive
Current
Rating Code
DC
Amps
AC
Line
Amps
Qty Bussmann Ferraz Shawmut (Gould Shawmut) SIBA
Square Body - Flush End Contact
C 521 521 426 3 170M5466 + switch 170H0069 6,9 URD 32 TTF 1000 + switch MS 3-V1-5 BS 20 671 32.1000 + switch 28 001 04
700 700 571 3 170M5466 + switch 170H0069 6,9 URD 32 TTF 1000 + switch MS 3V 1-5 BS 20 671 32.1000 + switch 28 001 04