Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012 77
Drive Comparisons Chapter 1
PowerFlex DC - Armature Power Connections
PowerFlex DC Armature Power Terminal and Ground (PE) Wire Sizes
Figure 43 - PowerFlex DC - Frame A Armature Terminal Block Location
Terminals Description
U, V, W Three phase AC input to the armature converter
C, D DC output to the motor armature
PE Safety ground
Frame Drive Current Rating Code
(1)
Terminals Wire Size and Type Terminal
Bolt Size
(mm)
Tightening
Torque
Nm (lbin)
230V 460V 575 690
A 7P0…055 4P1…052 U, V, W, C, D, PE See “Cable and Wiring
Recommendations” in
the PowerFlex Digital
DC Drive User Manual,
publication
20P-UM001.
56 (53)
073…110 073…129 Terminal Block 12 (106)
B All All U, V, W, C, D 10 25 (221)
PE 8 15 (132.75)
C All All U, V, W, C, D 10 25 (221)
PE 8 15 (132.75)
D All All All All U, V, W, C, D, PE 12 45 (398.2)
(1) See PowerFlex Digital DC Drive on page 28, positions 8, 9 and 10 for corresponding drive HP rating, armature amp rating and field amp rating.
UC V DWPE
Front View