74 Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012
Chapter 1 Drive Comparisons
PowerFlex DC Drive Typical Power Wiring Diagrams
The following diagram represents recommended power wiring configurations:
Figure 40 - Power Wiring with AC Input Contactor
M
C
D
Aux
PowerFlex DC
Drive
36
(8)
34
(4)
(on I/O TB4)
19
(5)
(+24V on I/O TB2)
(N.O. Relay)
M1 AC Contactor
Control
Board P/S
AC Input
Voltage
115V
or
230V
(1)
V2
U2
F2
A1
A2
35
(8)
U
V
W
3 Phase
AC line
L1
L2
L3
13 14
L1
L2
L3
A1
T1
T2
T3
A2
U1
V1
C1
D1
F1
FS2
(6)
FS2
(6)
FS1
(3)
FS1
(3)
FS1
(3)
FU1
FV1
FU FU
Field Power Terminal Block
Control Power / Relay
Terminal Block
A1
A2
Armature Volt.
Fdbk. Term.
(7)
1A1
1A2
U3
V3
Fan Power Terminal Block
(9)
230V
FU FU
Line Reactor
(2)
Isolation
Transformer
(2)
Lockable
Installation
Disconnect
SB
(1)
SA
(1)
These connections
must be taken from
the primary side of
the Isolation Transformer
or Line Reactor
(clean power).
AC Input
Voltage
PE
Safety Ground
AC Input
Voltage
460 VAC
Max. or
230 VAC
Min.
(10)
(1) For frame B and C drives only, a jumper is required between terminals SA and SB for 115V AC control input power. See PowerFlex DC Control Circuit Power Connections on page 87 for more information.
(2) An Isolation Transformer and/or 3…5% impedance Line Reactor is required. If the Isolation Transformer provides the required 3…5% impedance, a Line Reactor is not required. See Appendix A in the PowerFlex Digital DC Drive User
Manual, publication 20P-UM001
, for recommendations.
(3) AC input fuses for the armature converter are customer supplied for frame A and B drives and are internally mounted on frame C and D drives. See PowerFlex DC Drives Circuit Protection on page 139
for fuse recommendations.
(4) Par 140 [Digital In8 Sel] set to 31 “Contactor”
(5) If using the +24V internal power supply, terminal 18 (24V common) must be jumpered to terminal 35 (digital input common).
(6) Customer supplied armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. See PowerFlex DC Drives Circuit Protection on page 139
for fuse recommendations.
(7) Optional armature voltage feedback sensing not required with AC contactor.
(8) Par 1391 [ContactorControl] = 1 “AC Cntctr” and Par 1392 [Relay Out 1 Sel] = 25 “Contactor”. Important: Terminal 35 and 36 are on the Control Power / Relay Terminal block, NOT the I/O terminal blocks. See PowerFlex DC I/O Signal
and Control Wiring on page 118 for locations.
(9) Frame C & D drives only require an external power supply for the heatsink cooling fan. See PowerFlex DC Frame C Heatsink Cooling Fans Power Supply Terminals on page 91
and PowerFlex DC Frame D Heatsink Cooling Fans Power
Supply Terminals on page 92 for more information.
(10) See PowerFlex DC Field Converter Connections on page 84
.