Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012 147
Drive Comparisons Chapter 1
Frame C and D Recommended Field Circuit Fuses
Field circuit fuses for frames C and D drives are internally mounted (labeled FU1
and FV1) and provided with the drive. See Fuse Code FS3 in Frame C and D
Fuse Designations on page 146
. Also, see Frame C Field Circuit Fuse Location on
page 148
and Frame D Field Circuit Fuse Location on page 149 for locations.
Table 45 - 230V AC Input Drives
Table 46 - 460V AC Input Drives
Table 47 - 575V AC Input Drives
Frame Drive
Current
Rating Code
Field
Amps
Type Qty Bussmann Ferraz Shawmut
(Gould Shawmut)
SIBA
C 521 20 10 x 38 mm 2 FWC-25A10F A60Q25-2 6003305.25
D 875 40 22 x 58 mm FWP-50A22F A70QS50-22F 5014006.50
1K0
Frame Drive
Current
Rating Code
Field
Amps
Type Qty Bussmann Ferraz Shawmut
(Gould Shawmut)
SIBA
C 495 20 10 x 38 mm 2 FWC-25A10F A60Q25-2 6003305.25
667 A60Q25-8
D 830 40 22 x 58 mm FWP-50A22F A70QS50-22F 5014006.50
996
1K1 70 FWP-100A22F A70QS100-22F 5014006.100
1K3
1K4
Frame Drive
Current
Rating
Code
Field
Amps
Type Qty Bussmann Ferraz Shawmut
(Gould Shawmut)
SIBA
C 540 20 10 x 38 mm 2 FWC-25A10F A60Q25-2 6003305.25
675 A60Q25-8
D 810 40 22 x 58 mm FWP-50A22F A70QS50-22F 5014006.50
1K0
1K2
1K3
1K6