172 Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012
Chapter 2 Wiring Examples
Figure 120 - Two-wire Control with Preset Speeds
Run
Stop/CF
Speed Select 2
16
15
14
13
31
37
38
39
40
11
12
35
36
32
34
33
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
Not Used
17
18
20
19
Not Used
+24V DC Supply
Digital Input Common
24V Supply Common
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Not Used
Digital Input Common
Not Used
Not Used
Not Used
PE Ground
Internal 0V (Grd)
PowerFlex DC
TB2
TB4
+24V
Neutral /
Common
• Conguration
P133 [Digital In1 Sel] is kept at its default of “Stop/CF”.
P134 [Digital In2 Sel] = 5 “Run”
P137 [Digital In5 Sel] = 17 “Speed Sel 1”
P138 [Digital In6 Sel] = 18 “Speed Sel 2”
P44 [Speed Ref A]
P48 [Speed Ref B]
P155 [Preset Speed 2]
P156 [Preset Speed 3]
Note: If Digital Input 5 & 6 are open, then the drive uses
P44 [Speed Ref A] as it’s speed reference.
- Refer to the PowerFlex DC User Manual,
Publication 20-p-um001, for more details on wiring
examples, Digital Input conguration and Speed Reference
selection.
( User Supplied )
NOTE: If your drive utilizes 115 VAC Inputs, refer to the
PowerFlex DC user manual, Appendix G for details on the
115V AC to 24V DC I/O Converter Circuit Board.
Speed Select 1
22
21
20
19
18
17
15
14
13
1
7
8
9
10
11
12
23
24
5
6
2
4
3
27
26
25
30
29
28
Analog Out Common
Analog Out 2
1397 Regulator Board with I/O Expansion Card
16
+24VDC
Run
(1) (2)
Stop
(1)
Jog
(1)
Reverse / Forward
(1)
Reference Select
(1)
+24VDC
Coast-to-Stop
(1)
Customer Interlock
(1)
Fault Alarm Reset
+24VDC
Brush Wear
(1)
Motor Thermostat
(1)
+24VDC
+24VDC Common
+10VDC (Isolated)
Analog Reference 2 (+)
Analog Reference 2 (-)
Analog Reference 1 (+)
Analog Reference 1 (-)
Clear Fault
31
32
Analog Tachometer In (+)
Analog Tachometer In (-)
Analog Tachometer In (Com)
Analog Out 1
Running (N.O.)
Alarm (N.O.)
No Fault (N.O.)
• Conguration
P87 = [Preset Speed 1]
P88 = [Preset Speed 2]
P89 = [Preset Speed 3]
(1) Require for initial startup and
operational checks. Voltage must be
present at these points during operation. In
other words, these terminals must be made.
If open, the drive will be ‘Not Ready’.
(2) RUN – Edge sensitive signal that
initiates a Run command (0 1 = Run). If
the Drive is Run, voltage may be applied to
the armature causing the motor to reach the
desired speed.
RUN/STOP by
user contact
64
63
62
61
60
59
57
56
55
38
44
50
51
52
53
54
65
66
42
43
39
41
40
69
68
67
Dig Out 1 Com
Dig Out 2
58
Unused
Freq In A
Freq In A (not)
Com
Freq Out A
Freq Out A (not)
Com
Anlg In 3 (+)
Anlg In 3 (-)
Anlg In 4 (+)
Anlg In 4 (-)
Anlg Out 3 (+)
Anlg Out 3 (-)
Anlg Out 4 (+)
+24V DC
Preset Speed B
Preset Speed A
+24V DC
MOP Decrement
MOP Increment
OCL Enable
24V Com
Dig Out 1
33
34
Anlg Out 4 (-)
Dig Out 2 Com
10V DC
Gnd
Preset Speed A
Preset Speed B
NOTE: Install the I/O Expansion
Board in the drive carrier using the (2)
pan head screws provided, then plug
the middle ribbon cable connector into
J1.
- Refer to the 1397–L11
I/O Expansion Card, Publication 1397-
in008 for more details.
Two-wire Control, Preset Speeds