Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012 167
Wiring Examples Chapter 2
Figure 116 - Two-wire Control with an Analog Input Speed Reference
16
15
14
13
1
7
8
9
10
11
12
5
6
2
4
3
Analog In 1 (+)
Analog In 1 (-)
Analog In 2 (+)
Analog In 2 (+)
Pot Common
17
18
20
19
- 10V Pot Reference
+24V DC Supply
Digital Input Common
24V Supply Common
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
+ 10V Pot Reference
PowerFlex DC
Analog Input 3 (+)
Analog Input 3 (-)
Pot Ground
Not Used
PE Ground
Internal 0V (Grd)
• Conguration:
P1322 [Direction Mode] = 1 “Bipolar”
P70 [Anlg in1 Sel] = Speed Ref A
P71 [Anlg In1 Cfg] = +/- 10
Note: DIP switch S9 should be
set to “On”
P133 [Digital In1 Sel] is kept at its default of “Stop/CF”.
P134 [Digital In2 Sel] = 5 “Run”
- Refer to the PowerFlex DC User Manual, Publication
20-p-um001, Chapter 1: Installation and Wiring, for more
details on wiring examples.
• Adjust Scaling:
P72 [Anlg In1 Scale]
P73 [Anlg1 Tune Scale]
• View Signal Value:
P1404 [Analog In1 Value]
• View Signal Output:
P385 [Speed Ref Out]
TB1
TB2
44
43
42
41
40
39
37
36
35
23
29
30
31
32
33
34
45
46
27
28
24
26
25
49
48
47
52
51
50
Digital Input Common
Digital Input 1
Digital Input 3
Digital Input 4
Not Used
Digital Input 2
1395 Discrete Adapter Board
(Mounted in Port A)
38
TB3
Analog Input 4 (-)
Analog Input 4 (+)
Analog Input 3 (-)
Analog Input 3 (+)
Analog Input 2 (-)
Analog Input 2 (+)
Analog Input 1 (-)
Analog Input 1 (+)
-10 VDC
+10 VDC
Common
Analog Output 4 (-)
Analog Output 3 (+)
Analog Output 2 (-)
Analog Output 1 (+)
Analog Output 4 (Common)
Analog Output 3 (Common)
Analog Output 2 (Common)
Analog Output 1 (Common)
Not Used
Digital Output 2
Digital Output 1
50
49
48
47
46
45
43
42
41
29
35
36
37
38
39
40
51
52
33
34
30
32
31
55
54
53
58
57
56
Digital Input Common
Digital Input 1
Digital Input 3
Digital Input 4
Not Used
Digital Input 2
1395 Digital Reference Adapter Board
(Mounted in Port A)
44
TB3
Analog Input 2 (-)
Analog Input 2 (+)
Analog Input 1 (-)
Analog Input 1 (+)
-10 VDC Reference
+10 VDC Reference
Reference Common
Analog Output 1 (Out)
23
27
28
24
26
25
59
60
61
62
Encoder In Ch A
Encoder In Ch Anot
Encoder In Ch B
Encoder In Ch Bnot
Not Used
Not Used
Not Used
Not Used
Not Used
Analog Output 1 (Common)
Analog Output 2 (Out)
Analog Output 2 (Common)
Digital Input 5
Digital Input 7
Digital Input 8
Digital Input 6
Digital Input 9
Digital Input 10
Digital Output 1
Digital Output 2
Digital Output 3
Digital Output 4
Not Used
Digital Output 5
+24V DC Input ISOL
+24V DC Common
NOTE: If your 1395 drive utilizes 115 VAC Inputs, refer to
the PowerFlex DC user manual, Appendix G for details on
the 115V AC to 24V DC I/O Converter Circuit Board.
Neutral /
Common
( User Supplied )
Stop/CF
Run
+24V
Neutral /
Common
( User Supplied )
• Conguration:
P624 [Maintained Start] = 1 “Maintained”.
- Refer to the 1395 User Manual, Chapter 7:
Programming Parameters, for more details on
control.
• P401 [Analog Input 1] linked to P154 [External
Velocity]
P583 [Digital Input 1] is programmed for “Stop”
(Logic Command Word Bit 11)
P585 [Digital Input 3] is programmed for “Start”
(Logic Command Word Bit 12)
P586 [Digital Input 4] is programmed for “Clear
Fault” (Logic Command Word Bit 14)
• Scaling: +/- 10 VDC = +/- 100% Base Speed
P551 [A>ADC Oset 1] = 0
P550 [A>ADC Scale 1] = 2
- Refer to the 1395 Discrete Adapter Board
Installation & Operation Manual, Publication
1395-in001, Chapter 5: Start-Up, for more details
on scaling examples.
• Conguration:
P624 [Maintained Start] = 1 “Maintained”.
- Refer to the 1395 User Manual, Chapter 7:
Programming Parameters, for more details on
control.
P401 [Analog Input 1] linked to P154 [External
Velocity]
P583 [Digital Input 1] is programmed for “Stop”
(Logic Command Word Bit 11)
P585 [Digital Input 3] is programmed for “Start”
(Logic Command Word Bit 12)
P586 [Digital Input 4] is programmed for “Clear
Fault” (Logic Command Word Bit 14)
• Scaling: +/- 10 VDC = +/- 100% Base Speed
P551 [A>ADC Oset 1] = 0
P550 [A>ADC Scale 1] = 2
- Refer to the 1395 Discrete Adapter Board
Installation & Operation Manual, Publication
1395-in001, Chapter 5: Start-Up, for more details
on scaling examples.
Stop
Start
+24V
Neutral /
Common
( User Supplied )
Clear Fault
Stop
Start
+24V
Clear Fault
Two-wire Control, Analog Input Ref