168 Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012
Chapter 2 Wiring Examples
Figure 117 - Two-wire Control with Preset Speeds
Run
Stop/CF
Speed Select 2
16
15
14
13
31
37
38
39
40
11
12
35
36
32
34
33
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
Not Used
17
18
20
19
Not Used
+24V DC Supply
Digital Input Common
24V Supply Common
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Not Used
Digital Input Common
Not Used
Not Used
Not Used
PE Ground
Internal 0V (Grd)
PowerFlex DC
TB2
TB4
+24V
Neutral /
Common
• Conguration:
P133 [Digital In1 Sel] is kept at its default of
“Stop/CF”.
P134 [Digital In2 Sel] = 5 “Run”
P137 [Digital In5 Sel] = 17 “Speed Sel 1”
P138 [Digital In6 Sel] = 18 “Speed Sel 2”
P48 [Speed Ref B]
P155 [Preset Speed 2]
P156 [Preset Speed 3]
Note: If Digital Input 5 & 6 are open, then the
drive uses P44 [Speed Ref A] as it’s speed
reference.
- Refer to the PowerFlex DC User
Manual, Publication 20-p-um001, for more
details on wiring examples, Digital Input
conguration and Speed Reference selection.
( User Supplied )
44
43
42
41
40
39
37
36
35
23
29
30
31
32
33
34
45
46
27
28
24
26
25
49
48
47
52
51
50
Digital Input Common
Digital Input 1
Digital Input 3
Digital Input 4
Not Used
Digital Input 2
1395 Discrete Adapter Board (Mounted in Port A)
38
TB3
Analog Input 4 (-)
Analog Input 4 (+)
Analog Input 3 (-)
Analog Input 3 (+)
Analog Input 2 (-)
Analog Input 2 (+)
Analog Input 1 (-)
Analog Input 1 (+)
-10 VDC
+10 VDC
Common
Analog Output 4 (-)
Analog Output 3 (+)
Analog Output 2 (-)
Analog Output 1 (+)
Analog Output 4 (Common)
Analog Output 3 (Common)
Analog Output 2 (Common)
Analog Output 1 (Common)
Not Used
Digital Output 2
Digital Output 1
50
49
48
47
46
45
43
42
41
29
35
36
37
38
39
40
51
52
33
34
30
32
31
55
54
53
58
57
56
Digital Input Common
Digital Input 1
Digital Input 3
Digital Input 4
Not Used
Digital Input 2
1395 Digital Reference Adapter Board
(Mounted in Port A)
44
TB3
Analog Input 2 (-)
Analog Input 2 (+)
Analog Input 1 (-)
Analog Input 1 (+)
-10 VDC Reference
+10 VDC Reference
Reference Common
Analog Output 1 (Out)
23
27
28
24
26
25
59
60
61
62
Encoder In Ch A
Encoder In Ch Anot
Encoder In Ch B
Encoder In Ch Bnot
Not Used
Not Used
Not Used
Not Used
Not Used
Analog Output 1 (Common)
Analog Output 2 (Out)
Analog Output 2 (Common)
Digital Input 5
Digital Input 7
Digital Input 8
Digital Input 6
Digital Input 9
Digital Input 10
Digital Output 1
Digital Output 2
Digital Output 3
Digital Output 4
Not Used
Digital Output 5
+24V DC Input ISOL
+24V DC Common
NOTE: If your 1395 drive utilizes 115 VAC Inputs, refer to
the PowerFlex DC user manual, Appendix G for details on
the 115V AC to 24V DC I/O Converter Circuit Board.
Stop
Start
+24V
Neutral /
Common
( User Supplied )
Run Reference Select A
Neutral /
Common
( User Supplied )
Stop
Start
+24V
Run Reference Select B
Run Reference Select B
Run Reference Select A
Speed Select 1
• Conguration:
P624 [Maintained Start] = 1 “Maintained”.
- Refer to the 1395 User Manual, Chapter 7:
Programming Parameters, for more details on control.
P583 [Digital Input 1] is programmed for “Stop” (Logic
Command Word Bit 11)
P584 [Digital Input 2] is programmed for “Run
Reference Select A” (Logic Command Word Bit 0)
P585 [Digital Input 3] is programmed for “Start”
(Logic Command Word Bit 12)
P584 [Digital Input 4] is programmed for “Run
Reference Select B” (Logic Command Word Bit 1)
P633 [Preset Speed 1]
P634 [Preset Speed 2]
P635 [Preset Speed 3]
Note: If Digital Input 2 & 4 are open, the drive uses
P154 [Vel Ref Whole] as it’s speed reference.
• Conguration:
P624 [Maintained Start] = 1 “Maintained”.
- Refer to the 1395 User Manual, Chapter 7:
Programming Parameters, for more details on control.
P583 [Digital Input 1] is programmed for “Stop” (Logic
Command Word Bit 11)
P585 [Digital Input 3] is programmed for “Start”
(Logic Command Word Bit 12)
P590 [Digital Input 8] is programmed for “Run
Reference Select A” (Logic Command Word Bit 0)
P591 [Digital Input 9] is programmed for “Run
Reference Select B” (Logic Command Word Bit 1)
P633 [Preset Speed 1]
P634 [Preset Speed 2]
P635 [Preset Speed 3]
Note: If Digital Input 2 & 4 are open, the drive uses
P154 [Vel Ref Whole] as it’s speed reference.
Two-wire Control, Preset Speeds