Frame A and B Recommended Armature DC Output Fuses
Armature DC output fuses are externally mounted for frame A and B drives and
must be sourced separately. These fuses are required on four quadrant drives only,
but highly recommended on two quadrant drives. See Fuse Code FS2 in
Figure 100
on page 139.
Table 39 - 230V AC Input Drives
Frame Drive Current
Rating Code
DC
Amps
AC
Line
Amps
Bussmann Ferraz Shawmut (Gould Shawmut)
Ferrule FWP
Type
Ferrule
Fuse Block
North American
FWP Type
North American
Fuse Block
Ferrule A70QS
Type
North American
A70P / A70QS Type
A 7P0 7 5.7 FWP-15A14F CH142D FWP-15B – A70QS16-14F A70P15-4
9P0 9 7.4 FWP-20A14F FWP-20B – A70QS20-14F A70P20-4
012 12 9.8 FWP-25A14F FWP-25B – A70QS25-14F A70P25-4
020 20 16 FWP-40A14F FWP-40B – A70QS40-14F A70QS40-4
029 29 24 FWP-63A22F CH222D FWP-60B – A70QS63-22F A70QS60-4
038 38 31 FWP-80A22F FWP-80B – A70QS80-22F A70QS80-4
055 55 45 – – FWP-125A BH-1133 – A70QS125-4K
073 73 60 – – FWP-150A – A70QS150-4K
093 93 76 – – FWP-200A – A70QS200-4K
110 110 90 – – FWP-225A – A70QS250-4
B 146 146 119 – – FWP-300A – A70QS300-4
180 180 147 – – FWP-350A – A70QS350-4
218 218 178 – – FWP-450A BH-3144 – A70QS450-4
265 265 217 – – FWP-600A – A70QS600-4K
360 360 294 – – FWP-700A – A70QS700-4
434 434 355 – – FWP-900A – A70P900-4